Provisions on fire control management of oil depot
Provisions on safety management of oil depots I. General provisions
1. It is strictly forbidden to bring inflammable and explosive articles such as matches, lighters and cigarettes into the warehouse;
2. It is forbidden for all personnel to enter the warehouse and live in the museum for personal reasons;
3. Temporary construction personnel should receive safety education and wear temporary passes when entering the warehouse;
5. Anyone carrying goods into or out of the warehouse should be inspected and registered;
6. Non-explosion-proof mobile communication equipment is prohibited in explosive dangerous areas such as tank farm, loading and unloading operation area and pump room.
Provisions on safety management of oil depots II. Fire and explosion prevention
Safety signs and warning signs should be set in key parts such as tank farm, loading and unloading operation area, oil pump room, fire pump room, boiler room and power distribution room. When fire is used in the warehouse, the Regulations on Safety Management of Hot Work shall be strictly implemented, and the work permit and safety measures shall be handled. On what basis should the oil depot be built? Who uses it and who maintains it? Principles of implementation? Set personnel, equipment, responsibilities and goals? Management, to ensure the equipment in good condition, to achieve safe operation.
Provisions on safety management of oil depots. Lightning protection and electrostatic control
1. The lightning protection and anti-static facilities and devices of the oil depot shall meet the requirements of the design specifications;
2. Lightning protection and anti-static grounding devices shall be kept intact and effective. Lightning protection grounding, anti-static grounding, working grounding of electrical equipment, protective grounding and information system grounding When installing grounding devices, the grounding resistance should not be greater than 4Ω. ;
3. Railroad, oil pipeline, crane pipeline, steel trestle, etc. The railway oil loading and unloading facilities shall be equipotential connected and grounded according to the specifications, and the grounding resistance shall not be greater than 10? ;
4. The pressure storage tank is not equipped with lightning rod (wire), so it is not appropriate to install lightning arrester in the tank farm;
5. It is forbidden to use plastic barrels or containers made of insulating materials to fill or transport Class A and B oils.
6. It is not allowed to use the ruler, temperature measuring and sampling tools made of two different conductive materials for operation. When metal material is used, it should be bridged with the tank body, and it is not allowed to be yanked and lifted during operation;
Provisions on safety management of oil depots. Fire control management
The oil depot should conscientiously implement the Fire Protection Law of People's Republic of China (PRC), Regulations on Fire Safety Management and Regulations on Fire Protection Standards of CNPC, and implement them? Prevention first, combining prevention with elimination? Policy, adhere to the principle of combining full-time fire fighting with voluntary fire fighting, and do a good job in fire fighting.
Provisions on safety management of oil depot V. Configuration of fire fighting facilities
Workplaces and auxiliary production areas shall be equipped with fire safety signs and fire fighting equipment as required. Portable fire extinguishers set in the open air should be placed in hooks, brackets or special boxes, and should be waterproof, dustproof and moisture-proof. All kinds of fire extinguishers should be clearly marked and easily accessible, and should be regularly checked, inflated and replaced. Unqualified fire extinguishers should be scrapped and updated in time;
Provisions on safety management of oil depots. feed water system
1, there must be no aquatic plants and sundries in the fire pool, and anti-freezing measures should be taken in cold areas;
2. After the system is started, the cooling time for cooling water to reach the designated spray tank should not exceed 5min.
3. The underground water supply pipeline should be filled with water all the year round, the main valve should be kept normally open, and the pipeline should be flushed once every six months. 4. Fire hydrants should be inspected regularly, and a fire hydrant effluent test should be conducted once every quarter. There is no obstacle within 0/.5m from the fire hydrant/kloc-,the underground fire hydrant is clearly marked, and there is no water and sundries in the well;
5. The fire pump should rotate every day and run once a week, and the running time of system equipment should be no less than 15 minutes;
Provisions on safety management of oil depots. froth fire extinguishing system
1. After the system is started, the foam mixture should be sprayed to all oil tank foam generators in the control area for no more than 5 minutes;
- Previous article:Summary of volunteer activities of forest fire prevention
- Next article:What is saline-alkali land?
- Related articles
- Urgently beg for barbecue slogan
- Class and the loud slogan of class
- Garbage classification theme promotional slogans
- Songs about Arbor Day
- How does my world server set the game mode of the person who comes in, which is the default game mode for the first time to enter the server? How to let pirated players enter?
- How to write a work report for the raw material manager
- 100 short warning sentences for internal control and compliance
- Short sentences to pay tribute to epidemic volunteers
- Rural roads make agriculture more prosperous.
- What idioms with the word "line" are there?