Can indoor fire hydrants be removed?

No, if you want to move a fire hydrant, you need to apply to the fire department first, and changes can only be made after approval. Unauthorized modifications are illegal and violate fire protection laws. Indoor fire hydrant is an indoor pipe network that supplies water to the fire scene. It has a valve interface and is a fixed indoor fire-fighting facility in factories, warehouses, high-rise buildings, public buildings and ships. It is usually installed in the fire hydrant box and is connected with the fire hose and Water guns and other equipment are used together.

Indoor fire hydrants layout requirements:

1. In order to enable people on site to discover and use fire hydrants in a timely manner, indoor fire hydrants should be clearly marked. Fire hydrants should be painted red and should not be disguised as something else.

2. The height of the indoor fire hydrant spout from the ground should be 1.0m. In order to reduce local water head loss and facilitate operation, the water outlet direction should be underground or at an angle of 90° to the wall where the fire hydrant is installed.

3. The front room of the fire elevator is the offensive bridgehead for firefighters to enter the room to put out the fire. In order for firefighters to launch an attack on the fire scene or open a path, an indoor fire hydrant should be installed in the front room of the fire elevator.

4. In order to prevent freezing damage, indoor fire hydrants in cold storage should generally be located in halls or stairwells at room temperature. There should be a fire hydrant at the entrance of the cold storage into the stuffy roof to facilitate fighting fires in the top insulation layer.

5. Fire hydrants, water hoses and water guns of uniform specifications should be used in Tongyi buildings so that fire hydrants can be used to break glass in case of fire.

6. When the water pressure at the fire hydrant mouth exceeds 0.5Mpa, pressure relief facilities should be installed. The pressure reducing facility is generally a pressure reducing valve or a pressure reducing orifice plate.

7. For high-rise industrial and civil buildings and other ground-floor buildings where the water tank cannot meet the water pressure requirements of the fire hydrant at the most unfavorable point, a button to directly start the fire water pump should be installed at each fire hydrant so that the fire water pump can be started promptly and the supply When using water at the fire scene, the buttons should be equipped with protective facilities.