Joke Collection Website - Public benefit messages - How to deal with fire alarm signal in fire control room?
How to deal with fire alarm signal in fire control room?
I. Alarm procedure
1. If there is no fire, find out the alarm reason and take corresponding measures, and make records carefully.
(1) When the fire detector gives a false alarm, the reasons for the false alarm shall be found out: whether there is a lot of dust and smoke on the site; Whether the airflow speed is too large; Whether there is high frequency electromagnetic interference.
(2) When the "Manual Fire Alarm Button" alarms, find out who started the alarm and record it, and reset the "Manual Fire Alarm Button" at the same time.
Second, the fire confirmation procedure:
1. If there is a fire, check it on the spot. The personnel on duty should immediately give feedback to the fire control room through walkie-talkie or fire telephone, and use on-site fire fighting equipment to extinguish the fire.
2. The personnel on duty in the fire control room shall start relevant fire-fighting equipment according to the fire, notify relevant personnel to be present to put out the fire, and report to the leaders on duty in the mall. After the leaders agree, they shall call 1 19 to report to the fire department.
3. After confirming the fire, if the fire is large, the personnel on duty in the fire control room should control the following facilities:
(1) Stop the fan at the relevant position, close the fire damper and pay attention to receiving its feedback signal.
(2) Start the smoke exhaust fan and exhaust valve in relevant parts, and pay attention to receiving their feedback signals.
(3) If the fire-fighting linkage control cabinet is in manual state, start the spray pump and pay attention to the feedback signal, and at the same time pay attention to the action signals of water flow indicator, wet alarm valve and pressure switch; Start the fire pump and pay attention to the feedback signal.
(4) When the fire-fighting linkage control cabinet is in the automatic state, attention should be paid to whether the water flow indicator moves, whether the wet alarm valve moves, whether the pressure switch moves and whether the fire pump moves.
(5) Inform relevant personnel to close the fire doors at corresponding positions.
(6) Send control signals to force all elevators to stop at the first floor, and pay attention to receiving their feedback signals; If the control room can't control the elevator to stop on the first floor, assign a security guard to the first floor, turn on the elevator fire switch and stop the elevator on the first floor.
(7) Cut off the non-fire power supply at the fire site.
(8) Connect the fire alarm device and the fire accident broadcast according to the evacuation order.
Extended data
Fire control room management system
(a) the fire control room staff should strictly abide by the fire control room safety operation procedures and fire safety management system.
(two) the fire control room shall implement a 24-hour duty system to ensure the timely detection and accurate handling of fire and fault alarms.
(three) the fire control room staff shall not be less than 2 people per class.
(4) The personnel on duty of the automatic fire control system in the fire control room shall obtain the post operation certificate and hold relevant certificates, and keep them in the fire control room for future reference.
(5) The staff in the fire control room should take up their posts on time and do a good job of succession. Successors shall not leave their posts without authorization before arriving at their posts.
(6) The staff in the fire control room shall take up their posts on time, stick to their posts and earnestly perform their duties. It is not allowed to leave the post, cover the post or sleep in the post. It is forbidden to drink alcohol before duty, and it is forbidden to engage in recreational activities when on duty. If you can't take up your post due to special circumstances, you should ask for leave from the competent leader of the unit in advance. After approval, they will be replaced by people in the same position.
(7) Clear signs should be set at the entrance of the fire control room; The fire control room should be equipped with emergency lighting, fire extinguishers and other fire fighting equipment, and equipped with corresponding communication tools.
(eight) the fire control room staff should take good care of the fire control room facilities and keep the control room clean and tidy.
(9) Irrelevant personnel are prohibited from entering the fire control room and touching the equipment at will.
(10) The fire control room shall not store inflammable and explosive dangerous goods, pile up articles or sundries irrelevant to equipment operation, and shall not pass through electrical lines and pipelines irrelevant to the fire control room.
(eleven) it is forbidden to smoke or use open flames in the fire control room.
References:
Baidu Encyclopedia: Fire Control Room
- Previous article:Is it a love if Scorpio doesn't reply to text messages?
- Next article:What industry does the takeaway belong to?
- Related articles
- Thank the class teacher for his warm words.
- What are the difficulties in the process of electricity bill recovery? What measures should be taken?
- CITIC Premium has never had a loan. Why did you send a text message saying that you had borrowed money? What is the reason?
- Bank card deposit or withdrawal, or online consumption after sending text messages to mobile phones. Who knows what a text message is? Please elaborate.
- What will happen if Xiao Huang doesn't pay for his car?
- How to help parents check the balance of bank cards?
- I am a student of Jinan University. I want to buy a cheaper mobile phone card. Nice phone. I'd like a 3G package. Who recommends one?
- I just opened a margin account. Can I cancel the ordinary stock account?
- How to activate balance change reminder in ICBC Financial E-Link?
- Shengbei sent a text message saying he was preparing to file a lawsuit