Fire protection design of architectural design code for funeral parlour

7.1.1 The fire resistance rating of the funeral home building should not be lower than Grade II.

7.1.2 The fire zone of funeral home building should be reasonably divided according to the building function.

7.1.3 memorial rooms should be equipped with fire hoses, hoses and other facilities.

7.1.4 the setting of fire extinguishers in funeral parlours should comply with the current national standard "Code for Design of Fire Extinguishers in Buildings" (GBJ14).

7.1.5 The number of fire exits in the funeral area should be no less than 2 in each fire zone, and the average evacuation number of each fire exit should not exceed 25; The maximum distance from any point indoors to the nearest exit should not exceed 2.m m.

7.1.6 The total evacuation width of stairs and walkways in mourning hall should be calculated at not less than .65m per 1 people, but the minimum clear width should not be less than 1.8m m..

7.1.7 The net width of the evacuation inner door and the evacuation outer door of the mourning hall should not be less than 1.4m, and no threshold or step should be set.

7.1.8 outdoor fire hydrant fire extinguishing system should be set up.

7.1.9 the fire protection design of the funeral home building interior decoration should comply with the relevant provisions of the current national standard "Fire Protection Regulations for Building Interior Decoration Design" (GB 5222). 7.2.1 The fire hazard classification of the storage items in the ashes storage room shall be classified according to Item 2 of Category C in the current national standard Code for Fire Protection Design of Buildings (GBJ16).

7.2.2 The ashes storage room shall not use water fire extinguishing facilities, but shall be equipped with gas or dry powder fire extinguishing facilities and fire detectors at obvious locations according to the scale.

7.2.3 The maximum allowable building area of the fire compartment of the ashes storage room should not be greater than 8 ㎡ when it is a single floor; When the building height is below 24.m, each floor should not be greater than 5 ㎡; When the building height is greater than 24.m, each floor should not be greater than 3㎡.

7.2.4 The partition wall between the ashes storage room and other adjacent rooms should be a firewall.

7.2.5 There should be no less than two safety exits in each fire zone, and one exit should be directly outside.

7.2.6 The door on the firewall of the ashes storage room should be a Class A fire door. The fire door of the ashes storage room should be opened outwards, and its clear width should not be less than 1.4m, and no threshold should be set.

7.2.7 No step should be set in the indoor passage of the ashes storage room.

7.2.8 The vertically connected strip windows of the ashes storage building should not cross the upper and lower fire compartments, and the horizontally connected strip windows should not cross the adjacent fire compartments.

7.2.9 The storage rack in the ashes storage room should be made of flame retardant materials.

7.2.1 The decoration materials in the ashes storage room should be flame-retardant materials with combustion performance grade A..

7.2.11 The fire prevention distance between the ashes storage room and the memorial place should not be less than 15.m. 7.3.1 The cremation room shall conform to the provisions of Class D fortification in the current national standard Code for Fire Protection Design of Buildings (GBJ 16).

7.3.2 There should be no less than two safety exits in the cremation room.

7.3.3 The design of the oil depot should comply with the current national standard Code for Fire Protection Design of Buildings (GBJ 16), and anti-freezing measures should be taken in cold areas.

7.3.4 the fire protection distance between the oil storage tank and the cremator in the cremation room shall comply with the relevant provisions of the current national standard "Code for Fire Protection Design of Buildings" (GBJ 16).

7.3.5 A gas source emergency cut-off valve should be set outside the building in the cremation room with gas-fired cremation equipment.