Requirements for using temporary shelters

Requirements for the use of temporary shelters: the height of shelters should not be less than1.7m, and the edge of wastes should not be more than10cm from the ground. The distance between the barrier and the charged body should be 6 ~ 10 kV and not less than 350mm;; 20 ~ 35kV shall not be less than 600mm.

The mesh of fences should be between 20x20 and 40x 40(mm), the spacing between fences should not exceed 0.2m, and the height of fences in outdoor substations should generally not be less than 2.5m.

The barrier is used to separate the live and dead parts, and it is a barrier to prevent workers from touching or approaching the live body by mistake when overhauling substation equipment and other electrical equipment. When it is found that the maintenance safety distance is not enough, a fence safety isolation device should be set up.

The electrical equipment in the substation should be equipped with safety barriers, which may not meet the requirements of safe distance during normal inspection.

For example, if the transformer installed indoors or outdoors is close to the ground, a safety fence should be installed.

There are two kinds of extended data electrical protection barriers: fixed barrier and temporary barrier.

1, the fixed barrier is usually welded by metal parts; Temporary fences can be made of dry wood or replaced by ropes. Fixed barriers are usually installed in front of high-voltage and low-voltage electrical intervals, in front of control screens or around outdoor high-voltage equipment.

2. Temporary barriers should be installed in corridors, entrances and exits where power outage maintenance equipment is located, which are close to the work place or near places with electrical gaps or no traffic. It is usually made of dry bamboo and wood materials, such as railings, fences, slabs and nets.

Electrical protective barriers are generally made of dry wood or other insulating materials and are divided into three types: ordinary barriers, insulating baffles and insulating covers. It is used to protect expansion workers from accidental contact or too close to the live part, and also used as isolation measures when the maintenance part is not safe enough from the live part.

The purpose of installing barriers is to isolate the workplace from the charged area or the dangerous area in space, so as to prevent the workers from touching the charged equipment by mistake at wrong intervals. For high-voltage facilities, regardless of their own insulation and protection, appropriate protection measures must be taken.