What is the general size of a fire control room?

1. The operating distance in front of the equipment panel should not be less than 1.5m when arranged in a single row; and should not be less than 2m when arranged in a double row.

2. On the side where the on-duty personnel often work, the distance from the equipment panel to the wall should not be less than 3m.

3. The maintenance distance behind the equipment panel should not be less than 1m.

4. When the arrangement length of the equipment panel is greater than 4m, channels with a width of not less than 1m should be provided at both ends.

5. In fire control rooms that are shared with other weak current systems in the building, fire protection equipment should be centrally located and should be clearly separated from other equipment.

Extended information:

Main equipment:

The fire protection equipment installed in the fire control room should include fire alarm controllers, fire linkage controllers, and fire control room graphics Display devices, fire-fighting dedicated telephone switchboards, fire emergency broadcast control devices, fire emergency lighting and evacuation indication system control devices, fire power supply monitors and other equipment or combination equipment with corresponding functions.

The fire control room should be equipped with an outside telephone for fire alarm.

It is strictly prohibited to pass through electrical lines and pipelines that are not related to fire protection facilities in the fire control room.

Setting requirements

1. The fire resistance level of a separate fire control room should not be lower than Level 2;

2. A fire control room attached to a building The fire control room should be set up on the first floor or underground floor of the building (with waterproofing and flooding measures), and should be placed near the outer wall;

3. It should not be set up in areas with strong electromagnetic field interference and Near other rooms that may affect the normal operation of fire control equipment;

4. The evacuation door should lead directly to the outdoors or a safety exit;

5. The equipment composition in the fire control room and its impact on building fire protection The control and display functions of the facility and the function of transmitting relevant information to the remote monitoring system should comply with the current national standards "Design Specification for Automatic Fire Alarm Systems" GB50116 and "General Technical Requirements for Fire Control Rooms" GB25506.