How to formulate management measures for kindergarten fire emergency lights

Kindergarten Fire Safety Management System

1. Fire Safety Responsibilities

1. There is a fire safety leadership organization, a fire extinguishing and evacuation plan, and fire safety regulations signed at all levels. Safety responsibility letter with promotional slogans.

2. Develop a fire safety responsibility system and safe operating procedures.

3. The employees of the unit have reached the "three knowledges and two familiarities", that is, they know the characteristics of fire, know the key parts, know the location and performance of fire-extinguishing equipment, be familiar with job responsibilities, and be familiar with fire-extinguishing countermeasures.

4. Have sound fire prevention files and fire prevention inspection records to eliminate fire hazards in a timely manner.

2. Building fire protection

5. The fire resistance level of the kindergarten building should not be lower than Level 2 and should not exceed 3 floors: buildings above 200M2 must have two evacuation stairs, and the stairwell is Smoke proof stairwell.

6. The fire protection distance between kindergartens and flammable and explosive places should be less than 30 meters. There should be no less than two safety exits in kindergartens. The doors should open outwards and no steps are allowed at the exits.

7. Kindergarten should not be located directly above, below or adjacent to a garage. Kindergarten rooms should not be located in underground civil air defense projects or in underground or semi-underground buildings converted from civil air defense projects.

8. The maximum allowable distance from a kindergarten room door to an external exit or to a closed stairwell is: (1) 25M for a room located between two external exits or stairs; (2) located in a pocket Aisle or end rooms are 2 om.

9. Fire rooms, flammable material storage rooms, non-enclosed elevator shafts, and flammable gas pipelines cannot be attached to the safe evacuation stairwell.

10. A steam boiler room cannot be installed in the kindergarten.

3. Fire protection of electrical appliances

11. The distance between power switches, switches, and sockets in kindergartens should be no less than 1.3M from the ground, and the distance between lamp heads and the ground should not be less than 2M.

12. Fluorescent lamps and incandescent lamps exceeding 60W in schools should not be installed directly on combustible materials. The distance between incandescent lamps and combustible materials should not be less than 0.5M. Floor lamps and table lamps are not allowed to be used for lighting. Paper or other light bulbs cannot be used. Combustible materials block light.

13. Do not pull wires randomly in children's dormitories in kindergartens, and it is prohibited to use electric stoves, electric irons and other electrical appliances.

14. For kindergartens equipped with air conditioners, the air conditioners should have grounding wires. Inflammable items should not be piled around them. Curtains should not be placed on the air conditioners. The power supply terminal board and electricity meter should be expanded to meet the corresponding load.

IV. Fire-fighting facilities

15. Fire extinguishers should be complete and easy to use, with two fire extinguishers per 50m. There should be no more than 5 fire extinguishers and no less than 2 fire extinguishers at each place. l OM one, outdoor fire hydrants must be installed in stairwells and corridors.

16. Evacuation instructions are placed on the walls on both sides of the passage and at corners. The upper edge of the sign should not be greater than 1.0 from the ground. The distance between signs should not be greater than 20M. The distance between the end of the bag-shaped walkway and the signs should not be greater than 1 OMo

17. Kindergartens with a building area of ??more than 300M2 on each floor should install an automatic alarm system.