What are the acceptance requirements for the fire pump room?

What is the specific content of the acceptance requirements for the fire pump room? The following Zhong Da Consultation will answer your questions.

1, emergency lighting and emergency exit equipment of fire pump room should meet the design requirements.

2. The specifications, models and quantities of working pump, standby pump, suction pump, outlet pipe and pressure relief valve and signal valve on outlet pipe shall meet the design requirements. When the gate valve is installed on the outlet pipe, it should be locked in the normally open position.

3. The fire pump should adopt self-irrigation water diversion or other reliable water diversion measures.

4, fire pump outlet pipe should be installed on the test with the drain valve and drain pipe.

5, standby power supply, automatic switching device settings should comply with the design requirements.

6. In the pump room with fire-fighting air pressure water supply equipment, when the system air pressure drops to the design minimum pressure, the fire-fighting water pump should be started through the pressure switch signal.

7. The number of water inlet pipe positions of the fire pump adapter should meet the design requirements. The fire pump adapter should be water filling test, and the pressure and quantity of the most unfavorable points of the system should meet the design requirements.